Air changes per hour
API · /ventilation-api
Ventilation & Airflow API
Ventilation and airflow maths as an API, computed locally and deterministically. The air-changes endpoint relates the air changes per hour, the airflow in CFM and the room volume — ACH = CFM × 60 ÷ volume — and solves whichever you leave out (the volume can be given directly or as length × width × height), reporting the airflow in cubic metres per hour too. The required-cfm endpoint applies the ASHRAE 62.1 breathing-zone rule, outdoor airflow = people × Rp + floor area × Ra, with sensible office defaults (5 CFM per person and 0.06 CFM per square foot), to size the fresh-air a space needs. The duct-velocity endpoint computes the air velocity in a round or rectangular duct from the flow and the duct size, V = CFM ÷ area, in feet per minute, metres per second and miles per hour, with guidance on whether it is in the quiet residential or noisier high-velocity range. Everything is computed locally and deterministically, so it is instant and private. Ideal for HVAC, building-services, indoor-air-quality and facilities app developers, ventilation-sizing and duct-design tools, and engineering education. Pure local computation — no key, no third-party service, instant. Live, nothing stored. 3 endpoints. This is ventilation and airflow; for heating and cooling load sizing use an HVAC API.
API salute
salutare- Tempo di attività
- 100.00%
- Sondaggi del server · 24 ore su 24
- Latenza media
- 75 ms
- Sondaggi del server · 24 ore su 24
- Abbonati
- 3,404
- attiva
- Chiamate totali
- 76
- ultimi 7 giorni
Prezzi
Scegli un livello: fatturazione mensile, annullamento in qualsiasi momento.
Free
Gratis
- 2,000 chiamate/mese
- 2 richieste/secondo
- Tetto rigido (429 sopra la quota, nessuna eccedenza)
- 26,735 calls/month
- 2 req/sec
- Air changes + required CFM + duct
- No credit card
Starter
€9.00 /mese
- 30,000 chiamate/mese
- 5 richieste/secondo
- Tetto rigido (429 sopra la quota, nessuna eccedenza)
- 38.05k calls/month
- 8 req/sec
- ASHRAE rates, round & rectangular ducts
- Email support
Pro
€24.00 /mese
- 150,000 chiamate/mese
- 15 richieste/secondo
- Tetto rigido (429 sopra la quota, nessuna eccedenza)
- 414.5k calls/month
- 20 req/sec
- HVAC & duct-design pipelines
- Priority support
Mega
€69.00 /mese
- 750,000 chiamate/mese
- 40 richieste/secondo
- Tetto rigido (429 sopra la quota, nessuna eccedenza)
- 2.115M calls/month
- 50 req/sec
- Platform scale
- Dedicated SLA
Costruito da
Correlato APIs
Altro APIs con tag sovrapposti.
HVAC Ductwork API
HVAC-Kanaldimensionierungsmathematik als API, lokal und deterministisch berechnet – die Kanalabmessungen, mit denen ein Installateur oder Planer ein System dimensioniert, damit die Luft leise und effizient strömt. Der Rundkanal-Endpunkt gibt den runden Kanal für einen Luftstrom bei einer Zielgeschwindigkeit aus: Fläche = Luftstrom ÷ Geschwindigkeit (CFM ÷ ft/min = ft²), dann Durchmesser = √(4·Fläche/π) – 400 CFM bei einer Hauptgeschwindigkeit von 700 ft/min benötigt etwa einen 10,2-Zoll-Rundkanal, aufgerundet auf die nächste handelsübliche Größe von 12 Zoll. Der Geschwindigkeits-Endpunkt gibt die Luftgeschwindigkeit in einem Kanal aus Luftstrom und Größe an, rund oder rechteckig – 400 CFM durch einen 12 × 8 Kanal laufen mit 600 ft/min, angenehm leise, während die gleiche Luft in einem 10-Zoll-Rundkanal mit 733 ft/min strömt. Der Äquivalenz-Endpunkt gibt den äquivalenten runden Durchmesser eines rechteckigen Kanals nach der ASHRAE-Beziehung De = 1,30 · (a·b)^0,625 ÷ (a+b)^0,25 an, sodass ein 12 × 8 rechteckiger Kanal die gleiche Luft mit dem gleichen Reibungsverlust wie ein 10,7-Zoll-Rundkanal führt – so können Sie mit einer runden Reibungstabelle dimensionieren und an den verfügbaren Platz anpassen. Alles wird lokal und deterministisch berechnet, daher ist es sofort und privat. Ideal für HVAC-Design- und Installateur-Apps, Kanaldimensionierungs- und Auslegungswerkzeuge, Gebäudetechnik-Rechner und Berufsschulhilfen. Reine lokale Berechnung – kein Key, kein Drittanbieter-Service, sofort. Live, nichts wird gespeichert. 3 Compute-Endpunkte. Für Raumluftwechsel verwenden Sie eine Lüftungs-API; für die Kühl-/Heizlast verwenden Sie eine HVAC-API.
api.oanor.com/ductwork-api
HVAC Air-Side Load API
HVAC air-side heat maths as an API, computed locally and deterministically with the classic standard-air factors — the sensible, latent and airflow numbers a mechanical engineer or HVAC technician sizes ducts and equipment with. The sensible endpoint gives the sensible heat an airflow carries to change temperature: Qs = 1.08 × CFM × ΔT (dry-bulb difference), where the 1.08 bundles standard-air density and specific heat — 2,000 CFM across a 20 °F difference is 43,200 BTU/hr, 3.6 tons — with the result in BTU/hr, tons and kW. The latent endpoint gives the latent (moisture) heat: Ql = 0.68 × CFM × ΔW, where ΔW is the humidity-ratio difference in grains of water per pound of dry air, the dehumidification part of a cooling load that runs high in humid climates and from people and cooking, and why air conditioners are sized on total, not just temperature. The airflow endpoint inverts the sensible relation: CFM = sensible load ÷ (1.08 × ΔT), the supply air needed at a chosen supply-to-room temperature difference (comfort cooling runs ~18–22 °F below room), the number that sets fan and duct size — sanity-checked against ~400 CFM per ton. Everything is computed locally and deterministically, so it is instant and private. Ideal for HVAC-design and load-calc tools, mechanical-estimating and commissioning utilities, and building-engineering apps. Pure local computation — no key, no third-party service, instant. Standard-air factors — adjust for altitude. 3 compute endpoints. For room rule-of-thumb sizing use an HVAC API; for moist-air properties a psychrometric API; for duct sizing a ductwork API.
api.oanor.com/hvacload-api
Electric Motor FLA API
Electric-motor electrical maths as an API, computed locally and deterministically — the full-load-current, NEC-sizing and starting-current numbers an electrician, panel designer or estimator runs for every motor circuit. The full-load-amps endpoint gives the motor current from its power, voltage and phase: FLA = (output ÷ efficiency) ÷ (√3 × volts × power factor) for three-phase (drop the √3 for single-phase) — a 10 hp, 460 V, three-phase motor at 90 % efficiency and 0.85 power factor draws about 12.2 A — and it also returns the input kW and kVA. The sizing endpoint applies NEC Article 430 from the full-load current: branch-circuit conductors at 125 %, overload protection at 115–125 % by service factor, and branch-circuit short-circuit/ground-fault protection up to 250 % for an inverse-time breaker or 175 % for a time-delay fuse — the larger protection lets the inrush pass while the overload guards the windings. The starting endpoint gives the locked-rotor (inrush) current, about six times full-load for an across-the-line start, the figure that sets the voltage dip and why soft starters and VFDs exist. Everything is computed locally and deterministically, so it is instant and private. Ideal for electrical-design and estimating tools, panel-builder and field utilities, and engineering calculators. Pure local computation — no key, no third-party service, instant. Calculated values — use the NEC FLC tables for code work. 3 compute endpoints. For general three-phase power use a three-phase API; for conduit fill a conduit API.
api.oanor.com/motorfla-api
Heat Pump COP API
Heat-pump and refrigeration performance maths as an API, computed locally and deterministically — the efficiency numbers an HVAC engineer, energy auditor or heat-pump installer actually works with. The cop endpoint gives the coefficient of performance and the US EER rating from the thermal capacity and the electrical power: a unit moving 7 kW of heat on 2 kW of electricity has a COP of 3.5 (an EER of 12), meaning 3.5 units of heating or cooling for every unit of electricity — which is why a heat pump beats resistance heating, where the COP is exactly 1. The carnot endpoint gives the unbeatable ideal limit set only by the absolute temperatures — heating = Th ÷ (Th − Tc), cooling = Tc ÷ (Th − Tc) in kelvin, where heating COP always equals cooling COP plus one — and, given a real COP, the second-law efficiency that says how close the machine runs to that ceiling; the smaller the temperature lift, the higher the limit, which is why ground-source and low-temperature systems beat air-source on a cold day. The capacity endpoint turns electrical power and a COP into the delivered heating or cooling in kilowatts, BTU per hour and tons of refrigeration — the extra energy over the electricity is pulled from the outside air, ground or water. Everything is computed locally and deterministically, so it is instant and private. Ideal for HVAC and refrigeration engineers, energy auditors, heat-pump and building-performance tools, and sustainability dashboards. Pure local computation — no key, no third-party service, instant. Estimates at the stated conditions — real COP falls as the temperature lift rises. 3 compute endpoints. For room sizing use an HVAC BTU API; for moist-air properties use a psychrometric API.
api.oanor.com/heatpump-api
Domande frequenti
Risposte rapide su prezzi, quote e integrazione.
Come ottengo una chiave API per Ventilation & Airflow API?
Qual è il limite di velocità di Ventilation & Airflow API?
Quanto costa Ventilation & Airflow API?
Posso cancellare l'abbonamento in qualsiasi momento?
Ventilation & Airflow API è conforme al GDPR?
Scegli un endpoint dall'elenco a sinistra per visualizzarne i dettagli e provarlo.
Frammenti di codice
Iscriviti per ottenere una chiave API, quindi chiama qualsiasi percorso sotto il tuo slug.
curl https://api.oanor.com/ventilation-api/SOME_PATH \
-H "x-oanor-key: oanor_test_..."
const res = await fetch("https://api.oanor.com/ventilation-api/SOME_PATH", {
headers: { "x-oanor-key": "oanor_test_..." }
});
const data = await res.json();
$ch = curl_init("https://api.oanor.com/ventilation-api/SOME_PATH");
curl_setopt($ch, CURLOPT_RETURNTRANSFER, true);
curl_setopt($ch, CURLOPT_HTTPHEADER, ["x-oanor-key: oanor_test_..."]);
$response = curl_exec($ch);
import requests
r = requests.get(
"https://api.oanor.com/ventilation-api/SOME_PATH",
headers={"x-oanor-key": "oanor_test_..."},
)
print(r.json())
Valutazioni
Accedi per votare.
Nessuna recensione ancora.
Discussione
Fai domande, condividi consigli, ricevi risposte dal provider e dagli altri sviluppatori. Pubblico — chiunque può leggere.
Accedi per scrivere o rispondere.
AccediNuova discussione
·
-
Risposta del provider
🔒 Discussione bloccata — non si può più rispondere.
-
·
- Nessuna discussione — inizia tu.
Supporto
Supporto privato 1:1 con il provider — fatturazione, integrazione, account. Solo tu e il team del provider vedete questi thread.
Accedi per aprire un ticket di supporto.
AccediApri nuovo ticket
Descrivi cosa ti serve. Il team del provider riceve un'email e risponde sulla pagina del ticket.
-
·
Urgente - Nessun ticket per questa API.